UnderexcLimIEEE2
cim:UnderexcLimIEEE2
Type UEL2 underexcitation limiter which has either a straight-line or multi-segment characteristic when plotted in terms of machine reactive power output vs. real power output. Reference: IEEE UEL2 421.5-2005, 10.2 (limit characteristic lookup table shown in Figure 10.4 (p 32)).
Inherits from: UnderexcitationLimiterDynamics
Validations
tu1
UEL lead time constant (TU1) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tu2
UEL lag time constant (TU2) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tu3
UEL lead time constant (TU3) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tu4
UEL lag time constant (TU4) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tul
Time constant associated with optional integrator feedback input signal to UEL (TUL) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tup
Real power filter time constant (TUP) (>= 0). Typical value = 5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tuq
Reactive power filter time constant (TUQ) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tuv
Voltage filter time constant (TUV) (>= 0). Typical value = 5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)