StaticVarCompensator
cim:StaticVarCompensator
A facility for providing variable and controllable shunt reactive power. The SVC typically consists of a stepdown transformer, filter, thyristor-controlled reactor, and thyristor-switched capacitor arms.
The SVC may operate in fixed MVar output mode or in voltage control mode. When in voltage control mode, the output of the SVC will be proportional to the deviation of voltage at the controlled bus from the voltage setpoint. The SVC characteristic slope defines the proportion. If the voltage at the controlled bus is equal to the voltage setpoint, the SVC MVar output is zero.
Inherits from: RegulatingCondEq
Validations
capacitiveRating
Capacitive reactance at maximum capacitive reactive power. Shall always be positive.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
inductiveRating
Inductive reactance at maximum inductive reactive power. Shall always be negative.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
slope
The characteristics slope of an SVC defines how the reactive power output changes in proportion to the difference between the regulated bus voltage and the voltage setpoint. The attribute shall be a positive value or zero.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)