SiemensTM “H infinity” power system stabilizer with generator electrical power input. [Footnote: Siemens "H infinity" power system stabilizers are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Inherits from: PowerSystemStabilizerDynamics

Validations

t1

Time constant 1 (T1) (> 0). Typical value = 0,076.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t2

Time constant 2 (T2) (> 0). Typical value = 0,086.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t3

Time constant 3 (T3) (> 0). Typical value = 1,068.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t4

Time constant 4 (T4) (> 0). Typical value = 1,913.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

td

Input time constant (Td) (>= 0). Typical value = 10.

  • Minimum Value: 0.0