Skip to content

Pss2B

cim:Pss2B

Modified IEEE PSS2B. Extra lead/lag (or rate) block added at end (up to 4 lead/lags total).

Inherits from: PowerSystemStabilizerDynamics

Validations

t1

Lead/lag time constant (T1) (>= 0). Typical value = 0,12.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t10

Lead/lag time constant (T10) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t11

Lead/lag time constant (T11) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t2

Lead/lag time constant (T2) (>= 0). Typical value = 0,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t3

Lead/lag time constant (T3) (>= 0). Typical value = 0,3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t4

Lead/lag time constant (T4) (>= 0). Typical value = 0,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t6

Time constant on signal #1 (T6) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t7

Time constant on signal #2 (T7) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t8

Lead of ramp tracking filter (T8) (>= 0). Typical value = 0,2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t9

Lag of ramp tracking filter (T9) (>= 0). Typical value = 0,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ta

Lead constant (Ta) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tb

Lag time constant (Tb) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tw1

First washout on signal #1 (Tw1) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tw2

Second washout on signal #1 (Tw2) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tw3

First washout on signal #2 (Tw3) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tw4

Second washout on signal #2 (Tw4) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)