OverexcLimX2

cim:OverexcLimX2

Field voltage or current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.

Inherits from: OverexcitationLimiterDynamics

Validations

t1

Time to trip the exciter at the low voltage or current point on the inverse time characteristic (TIME1) (>= 0). Typical value = 120.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t2

Time to trip the exciter at the mid voltage or current point on the inverse time characteristic (TIME2) (>= 0). Typical value = 40.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t3

Time to trip the exciter at the high voltage or current point on the inverse time characteristic (TIME3) (>= 0). Typical value = 15.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vlow

Low voltage limit (VLOW) (> 0).

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)