OverexcLimX2
cim:OverexcLimX2
Field voltage or current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.
Inherits from: OverexcitationLimiterDynamics
Validations
t1
Time to trip the exciter at the low voltage or current point on the inverse time characteristic (TIME1) (>= 0). Typical value = 120.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t2
Time to trip the exciter at the mid voltage or current point on the inverse time characteristic (TIME2) (>= 0). Typical value = 40.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t3
Time to trip the exciter at the high voltage or current point on the inverse time characteristic (TIME3) (>= 0). Typical value = 15.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vlow
Low voltage limit (VLOW) (> 0).
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)