GovSteamFV4
cim:GovSteamFV4
Detailed electro-hydraulic governor for steam unit.
Inherits from: TurbineGovernorDynamics
Validations
ta
Control valves rate opening time (Ta) (>= 0). Typical value = 0,8.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tam
Intercept valves rate opening time (Tam) (>= 0). Typical value = 0,8.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Control valves rate closing time (Tc) (>= 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tcm
Intercept valves rate closing time (Tcm) (>= 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tdc
Derivative time constant of pressure regulator (Tdc) (>= 0). Typical value = 90.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf1
Time constant of fuel regulation (Tf1) (>= 0). Typical value = 10.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf2
Time constant of steam chest (Tf2) (>= 0). Typical value = 10.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
thp
High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,15.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tmp
Low pressure (LP) time constant of the turbine (Tmp) (>= 0). Typical value = 0,4.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
trh
Reheater time constant of the turbine (Trh) (>= 0). Typical value = 10.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tv
Boiler time constant (Tv) (>= 0). Typical value = 60.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ty
Control valves servo time constant (Ty) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)