Skip to content

GovSteamFV4

cim:GovSteamFV4

Detailed electro-hydraulic governor for steam unit.

Inherits from: TurbineGovernorDynamics

Validations

ta

Control valves rate opening time (Ta) (>= 0). Typical value = 0,8.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tam

Intercept valves rate opening time (Tam) (>= 0). Typical value = 0,8.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tc

Control valves rate closing time (Tc) (>= 0). Typical value = 0,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tcm

Intercept valves rate closing time (Tcm) (>= 0). Typical value = 0,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tdc

Derivative time constant of pressure regulator (Tdc) (>= 0). Typical value = 90.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tf1

Time constant of fuel regulation (Tf1) (>= 0). Typical value = 10.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tf2

Time constant of steam chest (Tf2) (>= 0). Typical value = 10.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

thp

High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,15.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tmp

Low pressure (LP) time constant of the turbine (Tmp) (>= 0). Typical value = 0,4.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

trh

Reheater time constant of the turbine (Trh) (>= 0). Typical value = 10.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tv

Boiler time constant (Tv) (>= 0). Typical value = 60.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ty

Control valves servo time constant (Ty) (>= 0). Typical value = 0,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)