GovHydroR
cim:GovHydroR
Fourth order lead-lag governor and hydro turbine.
Inherits from: TurbineGovernorDynamics
Validations
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t1
Lead time constant 1 (T1) (>= 0). Typical value = 1,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t2
Lag time constant 1 (T2) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t3
Lead time constant 2 (T3) (>= 0). Typical value = 1,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t4
Lag time constant 2 (T4) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t5
Lead time constant 3 (T5) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t6
Lag time constant 3 (T6) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t7
Lead time constant 4 (T7) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
t8
Lag time constant 4 (T8) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
td
Input filter time constant (Td) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tp
Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tt
Power feedback time constant (Tt) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tw
Water inertia time constant (Tw) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)