Skip to content

GovHydroPelton

cim:GovHydroPelton

Detailed hydro unit - Pelton model. This model can be used to represent the dynamic related to water tunnel and surge chamber. The DetailedHydroModelHydraulicSystem diagram, located under the GovHydroFrancis class, provides a schematic of the hydraulic system of detailed hydro unit models, such as Francis and Pelton.

Inherits from: TurbineGovernorDynamics

Validations

ta

Derivative gain (accelerometer time constant) (Ta) (>= 0). Typical value = 3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ts

Gate servo time constant (Ts) (>= 0). Typical value = 0,15.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tv

Servomotor integrator time constant (Tv) (>= 0). Typical value = 0,3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

twnc

Water inertia time constant (Twnc) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

twng

Water tunnel and surge chamber inertia time constant (Twng) (>= 0). Typical value = 3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tx

Electronic integrator time constant (Tx) (>= 0). Typical value = 0,5.

  • Minimum Value: 0.0