Skip to content

GovHydroIEEE2

cim:GovHydroIEEE2

IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors. Reference: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, Dynamic Models for Steam and Hydro Turbines in Power System Studies, page 1904.

Inherits from: TurbineGovernorDynamics

Validations

bturb

Turbine denominator multiplier (Bturb) (> 0). Typical value = 0,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tg

Gate servo time constant (Tg) (>= 0). Typical value = 0,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tp

Pilot servo valve time constant (Tp) (>= 0). Typical value = 0,03.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tr

Dashpot time constant (Tr) (>= 0). Typical value = 12.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tw

Water inertia time constant (Tw) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

uc

Maximum gate closing velocity (Uc) (<0). Typical value = -0,1.

  • Maximum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)