cim:GovHydroIEEE0

IEEE simplified hydro governor-turbine model. Used for mechanical-hydraulic and electro-hydraulic turbine governors, with or without steam feedback. Typical values given are for mechanical-hydraulic turbine-governor. Reference: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, Dynamic Models for Steam and Hydro Turbines in Power System Studies, page 1904.

Inherits from: TurbineGovernorDynamics

Validations

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t1

Governor lag time constant (T1) (>= 0). Typical value = 0,25.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t2

Governor lead time constant (T2) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t3

Gate actuator time constant (T3) (>= 0). Typical value = 0,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t4

Water starting time (T4) (>= 0).

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)