GovHydroDD
cim:GovHydroDD
Double derivative hydro governor and turbine.
Inherits from: TurbineGovernorDynamics
Validations
mwbase
Base for power values (MWbase) (>0). Unit = MW.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
td
Input filter time constant (Td) (>= 0). If = 0, block is bypassed. Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf
Washout time constant (Tf) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tp
Gate servo time constant (Tp) (>= 0). If = 0, block is bypassed. Typical value = 0,35.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tt
Power feedback time constant (Tt) (>= 0). If = 0, block is bypassed. Typical value = 0,02.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tturb
Turbine time constant (Tturb) (>= 0). See parameter detail 3. Typical value = 0,8.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)