GovHydro4
cim:GovHydro4
Hydro turbine and governor. Represents plants with straight-forward penstock configurations and hydraulic governors of the traditional 'dashpot' type. This model can be used to represent simple, Francis/Pelton or Kaplan turbines.
Inherits from: TurbineGovernorDynamics
Validations
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
rperm
Permanent droop (Rperm) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
rtemp
Temporary droop (Rtemp) (>= 0). Typical value = 0,3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tblade
Blade servo time constant (Tblade) (>= 0). Typical value = 100.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tg
Gate servo time constant (Tg) (> 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tp
Pilot servo time constant (Tp) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tr
Dashpot time constant (Tr) (>= 0). Typical value = 5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tw
Water inertia time constant (Tw) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)