GovHydro3
cim:GovHydro3
Modified IEEE hydro governor-turbine. This model differs from that defined in the IEEE modelling guideline paper in that the limits on gate position and velocity do not permit "wind up" of the upstream signals.
Inherits from: TurbineGovernorDynamics
Validations
at
Turbine gain (At) (>0). Typical value = 1,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
td
Input filter time constant (Td) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf
Washout time constant (Tf) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tp
Gate servo time constant (Tp) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tt
Power feedback time constant (Tt) (>= 0). Typical value = 0,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tw
Water inertia time constant (Tw) (>= 0). If = 0, block is bypassed. Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)