GovGAST4
cim:GovGAST4
Generic turbogas.
Inherits from: TurbineGovernorDynamics
Validations
ta
Maximum gate opening velocity (TA) (>= 0). Typical value = 3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Maximum gate closing velocity (TC) (>= 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tcm
Fuel control time constant (Tcm) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tm
Compressor discharge volume time constant (Tm) (>= 0). Typical value = 0,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ty
Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0