GovGAST3
cim:GovGAST3
Generic turbogas with acceleration and temperature controller.
Inherits from: TurbineGovernorDynamics
Validations
tac
Fuel control time constant (Tac) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
td
Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tg
Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tsi
Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ttc
Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ty
Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)