Generic turbogas with acceleration and temperature controller.

Inherits from: TurbineGovernorDynamics

Validations

tac

Fuel control time constant (Tac) (>= 0). Typical value = 0,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tc

Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

td

Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tg

Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tsi

Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ttc

Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ty

Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.

  • Minimum Value: 0.0