Skip to content

GovCT2

cim:GovCT2

General governor with frequency-dependent fuel flow limit. This model is a modification of the GovCT1 model in order to represent the frequency-dependent fuel flow limit of a specific gas turbine manufacturer.

Inherits from: TurbineGovernorDynamics

Validations

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ta

Acceleration limiter time constant (Ta) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tact

Actuator time constant (Tact) (>= 0). Typical value = 0,4.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tb

Turbine lag time constant (Tb) (>= 0). Typical value = 0,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tc

Turbine lead time constant (Tc) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tdgov

Governor derivative controller time constant (Tdgov) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

teng

Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (Teng) (>= 0). Teng should be zero in all but special cases where this transport delay is of particular concern. Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tfload

Load limiter time constant (Tfload) (>= 0). Typical value = 3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tpelec

Electrical power transducer time constant (Tpelec) (>= 0). Typical value = 2,5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tsa

Temperature detection lead time constant (Tsa) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tsb

Temperature detection lag time constant (Tsb) (>= 0). Typical value = 50.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)