GovCT1
cim:GovCT1
General model for any prime mover with a PID governor, used primarily for combustion turbine and combined cycle units. This model can be used to represent a variety of prime movers controlled by PID governors. It is suitable, for example, for the representation of:
- gas turbine and single shaft combined cycle turbines
- diesel engines with modern electronic or digital governors
- steam turbines where steam is supplied from a large boiler drum or a large header whose pressure is substantially constant over the period under study
- simple hydro turbines in dam configurations where the water column length is short and water inertia effects are minimal.
Additional information on this model is available in the 2012 IEEE report, Dynamic Models for Turbine-Governors in Power System Studies, 3.1.2.3 pages 3-4 (GGOV1).
Inherits from: TurbineGovernorDynamics
Validations
kturb
Turbine gain (Kturb) (> 0). Typical value = 1,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ta
Acceleration limiter time constant (Ta) (> 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tact
Actuator time constant (Tact) (>= 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb
Turbine lag time constant (Tb) (> 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Turbine lead time constant (Tc) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tdgov
Governor derivative controller time constant (Tdgov) (>= 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
teng
Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (Teng) (>= 0). Teng should be zero in all but special cases where this transport delay is of particular concern. Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tfload
Load-limiter time constant (Tfload) (> 0). Typical value = 3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tpelec
Electrical power transducer time constant (Tpelec) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tsa
Temperature detection lead time constant (Tsa) (>= 0). Typical value = 4.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tsb
Temperature detection lag time constant (Tsb) (>= 0). Typical value = 5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)