Skip to content

ExcRQB

cim:ExcRQB

Excitation system type RQB (four-loop regulator, r?gulateur quatre boucles, developed in France) primarily used in nuclear or thermal generating units. This excitation system shall be always used together with power system stabilizer type PssRQB.

Inherits from: ExcitationSystemDynamics

Validations

mesu

Voltage input time constant (MESU) (>= 0). Typical value = 0,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t4m

Input time constant (T4M) (>= 0). Typical value = 5.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tc

Lead lag time constant (TC) (>= 0). Typical value = 0,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

te

Lead lag time constant (TE) (>= 0). Typical value = 0,22.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tf

Exciter time constant (TF) (>= 0). Typical value = 0,01.

  • Minimum Value: 0.0