ExcREXS
cim:ExcREXS
General purpose rotating excitation system. This model can be used to represent a wide range of excitation systems whose DC power source is an AC or DC generator. It encompasses IEEE type AC1, AC2, DC1, and DC2 excitation system models.
Inherits from: ExcitationSystemDynamics
Validations
kf
Rate feedback gain (Kf) (>= 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ta
Voltage regulator time constant (Ta) (>= 0). If = 0, block is bypassed. Typical value = 0,01.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb1
Lag time constant (Tb1) (>= 0). If = 0, block is bypassed. Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb2
Lag time constant (Tb2) (>= 0). If = 0, block is bypassed. Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc1
Lead time constant (Tc1) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc2
Lead time constant (Tc2) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
te
Exciter field time constant (Te) (> 0). Typical value = 1,2.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf
Rate feedback time constant (Tf) (>= 0). If = 0, the feedback path is not used. Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf1
Feedback lead time constant (Tf1) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf2
Feedback lag time constant (Tf2) (>= 0). If = 0, block is bypassed. Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tp
Field current bridge time constant (Tp) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)