ExcIEEEDC3A
cim:ExcIEEEDC3A
IEEE 421.5-2005 type DC3A model. This model represents older systems, in particular those DC commutator exciters with non-continuously acting regulators that were commonly used before the development of the continuously acting varieties. These systems respond at basically two different rates, depending upon the magnitude of voltage error. For small errors, adjustment is made periodically with a signal to a motor-operated rheostat. Larger errors cause resistors to be quickly shorted or inserted and a strong forcing signal applied to the exciter. Continuous motion of the motor-operated rheostat occurs for these larger error signals, even though it is bypassed by contactor action. Reference: IEEE 421.5-2005, 5.3.
Inherits from: ExcitationSystemDynamics
Validations
efd1
Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 3,375.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
efd2
Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 3,15.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kv
Fast raise/lower contact setting (KV) (> 0). Typical value = 0,05.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seefd1
Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0,267.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seefd2
Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,068.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
te
Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,5.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
trh
Rheostat travel time (TRH) (> 0). Typical value = 20.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmax
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmin
Minimum voltage regulator output (VRMIN) (<= 0). Typical value = 0.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)