ExcIEEEDC1A
cim:ExcIEEEDC1A
IEEE 421.5-2005 type DC1A model. This model represents field-controlled DC commutator exciters with continuously acting voltage regulators (especially the direct-acting rheostatic, rotating amplifier, and magnetic amplifier types). Because this model has been widely implemented by the industry, it is sometimes used to represent other types of systems when detailed data for them are not available or when a simplified model is required. Reference: IEEE 421.5-2005, 5.1.
Inherits from: ExcitationSystemDynamics
Validations
efd1
Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 3,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
efd2
Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 2,3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ka
Voltage regulator gain (KA) (> 0). Typical value = 46.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kf
Excitation control system stabilizer gain (KF) (>= 0). Typical value = 0.1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seefd1
Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0.33.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seefd2
Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ta
Voltage regulator time constant (TA) (> 0). Typical value = 0,06.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb
Voltage regulator time constant (TB) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Voltage regulator time constant (TC) (>= 0). Typical value = 0.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
te
Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,46.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tf
Excitation control system stabilizer time constant (TF) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmin
Minimum voltage regulator output (VRMIN) (< 0 and < ExcIEEEDC1A.vrmax). Typical value = -0,9.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)