Skip to content

ExcIEEEAC7B

cim:ExcIEEEAC7B

IEEE 421.5-2005 type AC7B model. The model represents excitation systems which consist of an AC alternator with either stationary or rotating rectifiers to produce the DC field requirements. It is an upgrade to earlier AC excitation systems, which replace only the controls but retain the AC alternator and diode rectifier bridge. Reference: IEEE 421.5-2005, 6.7. Note, however, that in IEEE 421.5-2005, the [1 / sTE] block is shown as [1 / (1 + sTE)], which is incorrect.

Inherits from: ExcitationSystemDynamics

Validations

kc

Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,18.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kd

Demagnetizing factor, a function of exciter alternator reactances (KD) (>= 0). Typical value = 0,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kdr

Voltage regulator derivative gain (KDR) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kf1

Excitation control system stabilizer gain (KF1) (>= 0). Typical value = 0,212.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kf2

Excitation control system stabilizer gain (KF2) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kf3

Excitation control system stabilizer gain (KF3) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kia

Voltage regulator integral gain (KIA) (>= 0). Typical value = 59,69.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kir

Voltage regulator integral gain (KIR) (>= 0). Typical value = 4,24.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

kp

Potential circuit gain coefficient (KP) (> 0). Typical value = 4,96.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

seve1

Exciter saturation function value at the corresponding exciter voltage, VE1, back of commutating reactance (SE[VE1]) (>= 0). Typical value = 0,44.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

seve2

Exciter saturation function value at the corresponding exciter voltage, VE2, back of commutating reactance (SE[VE2]) (>= 0). Typical value = 0,075.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tdr

Lag time constant (TDR) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

te

Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 1,1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tf

Excitation control system stabilizer time constant (TF) (> 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vamax

Maximum voltage regulator output (VAMAX) (> 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vamin

Minimum voltage regulator output (VAMIN) (< 0). Typical value = -0,95.

  • Maximum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ve1

Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE1) (> 0). Typical value = 6,3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ve2

Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE2) (> 0). Typical value = 3,02.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vemin

Minimum exciter voltage output (VEMIN) (<= 0). Typical value = 0.

  • Maximum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vrmax

Maximum voltage regulator output (VRMAX) (> 0). Typical value = 5,79.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

vrmin

Minimum voltage regulator output (VRMIN) (< 0). Typical value = -5,79.

  • Maximum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)