ExcIEEEAC6A
cim:ExcIEEEAC6A
IEEE 421.5-2005 type AC6A model. The model represents field-controlled alternator-rectifier excitation systems with system-supplied electronic voltage regulators. The maximum output of the regulator, VR, is a function of terminal voltage, VT. The field current limiter included in the original model AC6A remains in the 2005 update. Reference: IEEE 421.5-2005, 6.6.
Inherits from: ExcitationSystemDynamics
Validations
ka
Voltage regulator gain (KA) (> 0). Typical value = 536.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kc
Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,173.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kd
Demagnetizing factor, a function of exciter alternator reactances (KD) (>= 0). Typical value = 1,91.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kh
Exciter field current limiter gain (KH) (>= 0). Typical value = 92.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seve1
Exciter saturation function value at the corresponding exciter voltage, VE1, back of commutating reactance (SE[VE1]) (>= 0). Typical value = 0,214.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seve2
Exciter saturation function value at the corresponding exciter voltage, VE2, back of commutating reactance (SE[VE2]) (>= 0). Typical value = 0,044.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ta
Voltage regulator time constant (TA) (>= 0). Typical value = 0,086.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb
Voltage regulator time constant (TB) (>= 0). Typical value = 9.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Voltage regulator time constant (TC) (>= 0). Typical value = 3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
te
Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
th
Exciter field current limiter time constant (TH) (> 0). Typical value = 0,08.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tj
Exciter field current limiter time constant (TJ) (>= 0). Typical value = 0,02.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tk
Voltage regulator time constant (TK) (>= 0). Typical value = 0,18.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vamax
Maximum voltage regulator output (VAMAX) (> 0). Typical value = 75.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vamin
Minimum voltage regulator output (VAMIN) (< 0). Typical value = -75.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ve1
Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE1) (> 0). Typical value = 7,4.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ve2
Exciter alternator output voltages back of commutating reactance at which saturation is defined (VE2) (> 0). Typical value = 5,55.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vfelim
Exciter field current limit reference (VFELIM) (> 0). Typical value = 19.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vhmax
Maximum field current limiter signal reference (VHMAX) (> 0). Typical value = 75.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmax
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 44.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmin
Minimum voltage regulator output (VRMIN) (< 0). Typical value = -36.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)