ExcHU
cim:ExcHU
Hungarian excitation system, with built-in voltage transducer.
Inherits from: ExcitationSystemDynamics
Validations
te
Major loop PI tag integration time constant (Te) (>= 0). Typical value = 0,154.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ti
Minor loop PI control tag integration time constant (Ti) (>= 0). Typical value = 0,01333.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tr
Filter time constant (Tr) (>= 0). If a voltage compensator is used in conjunction with this excitation system model, Tr should be set to 0. Typical value = 0,01.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)