Skip to content

ExcHU

cim:ExcHU

Hungarian excitation system, with built-in voltage transducer.

Inherits from: ExcitationSystemDynamics

Validations

te

Major loop PI tag integration time constant (Te) (>= 0). Typical value = 0,154.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ti

Minor loop PI control tag integration time constant (Ti) (>= 0). Typical value = 0,01333.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tr

Filter time constant (Tr) (>= 0). If a voltage compensator is used in conjunction with this excitation system model, Tr should be set to 0. Typical value = 0,01.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)