Skip to content

ExcELIN1

cim:ExcELIN1

Static PI transformer fed excitation system ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.

Inherits from: ExcitationSystemDynamics

Validations

tfi

Current transducer time constant (Tfi) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tnu

Controller reset time constant (Tnu) (>= 0). Typical value = 2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ts1

Stabilizer phase lag time constant (Ts1) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

ts2

Stabilizer filter time constant (Ts2) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tsw

Stabilizer parameters (Tsw) (>= 0). Typical value = 3.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

xe

Excitation transformer effective reactance (Xe) (>= 0). Xe represents the regulation of the transformer/rectifier unit. Typical value = 0,06.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)