Skip to content

ExcBBC

cim:ExcBBC

Transformer fed static excitation system (static with ABB regulator). This model represents a static excitation system in which a gated thyristor bridge fed by a transformer at the main generator terminals feeds the main generator directly.

Inherits from: ExcitationSystemDynamics

Validations

t1

Controller time constant (T1) (>= 0). Typical value = 6.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t2

Controller time constant (T2) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t3

Lead/lag time constant (T3) (>= 0). If = 0, block is bypassed. Typical value = 0,05.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

t4

Lead/lag time constant (T4) (>= 0). If = 0, block is bypassed. Typical value = 0,01.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

xe

Effective excitation transformer reactance (Xe) (>= 0). Xe models the regulation of the transformer/rectifier unit. Typical value = 0,05.

  • Minimum Value: 0.0