Skip to content

ExcAVR1

cim:ExcAVR1

Italian excitation system corresponding to IEEE (1968) type 1 model. It represents an exciter dynamo and electromechanical regulator.

Inherits from: ExcitationSystemDynamics

Validations

ta

AVR time constant (TA) (>= 0). Typical value = 0,2.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tb

AVR time constant (TB) (>= 0). Typical value = 0.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

te

Exciter time constant (TE) (>= 0). Typical value = 1.

  • Minimum Value: 0.0
  • Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)

tf

Rate feedback time constant (TF) (>= 0). Typical value = 1.

  • Minimum Value: 0.0