ExcAC6A
cim:ExcAC6A
Modified IEEE AC6A alternator-supplied rectifier excitation system with speed input.
Inherits from: ExcitationSystemDynamics
Validations
ka
Voltage regulator gain (Ka) (> 0). Typical value = 536.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kc
Rectifier loading factor proportional to commutating reactance (Kc) (>= 0). Typical value = 0,173.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kd
Demagnetizing factor, a function of exciter alternator reactances (Kd) (>= 0). Typical value = 1,91.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
kh
Exciter field current limiter gain (Kh) (>= 0). Typical value = 92.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seve1
Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0,214.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
seve2
Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 0,044.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ta
Voltage regulator time constant (Ta) (>= 0). Typical value = 0,086.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tb
Voltage regulator time constant (Tb) (>= 0). Typical value = 9.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tc
Voltage regulator time constant (Tc) (>= 0). Typical value = 3.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
te
Exciter time constant, integration rate associated with exciter control (Te) (> 0). Typical value = 1.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
th
Exciter field current limiter time constant (Th) (> 0). Typical value = 0,08.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tj
Exciter field current limiter time constant (Tj) (>= 0). Typical value = 0,02.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tk
Voltage regulator time constant (Tk) (>= 0). Typical value = 0,18.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vamax
Maximum voltage regulator output (Vamax) (> 0). Typical value = 75.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vamin
Minimum voltage regulator output (Vamin) (< 0). Typical value = -75.
- Maximum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ve1
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 7,4.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
ve2
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 5,55.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vfelim
Exciter field current limit reference (Vfelim) (> 0). Typical value = 19.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vhmax
Maximum field current limiter signal reference (Vhmax) (> 0). Typical value = 75.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmax
Maximum voltage regulator output (Vrmax) (> 0). Typical value = 44.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
vrmin
Minimum voltage regulator output (Vrmin) (< 0). Typical value = -36.
- Maximum Value: 0.0