DiscExcContIEEEDEC1A
cim:DiscExcContIEEEDEC1A
IEEE type DEC1A discontinuous excitation control model that boosts generator excitation to a level higher than that demanded by the voltage regulator and stabilizer immediately following a system fault. Reference: IEEE 421.5-2005, 12.2.
Inherits from: DiscontinuousExcitationControlDynamics
Validations
tan
Discontinuous controller time constant (TAN) (>= 0). Typical value = 0,08.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
td
Time constant (TD) (>= 0). Typical value = 0,03.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tl1
Time constant (TL1) (>= 0). Typical value = 0,025.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tl2
Time constant (TL2) (>= 0). Typical value = 1,25.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-302_Dynamics-AP-Con-Complex-SHACL_v3-0-0.ttl)
tw5
DEC washout time constant (TW5) (>= 0). Typical value = 5.
- Minimum Value: 0.0