ACDCConverter
cim:ACDCConverter
A unit with valves for three phases, together with unit control equipment, essential protective and switching devices, DC storage capacitors, phase reactors and auxiliaries, if any, used for conversion.
Inherits from: ConductingEquipment
Validations
baseS
Base apparent power of the converter pole. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
idleLoss
Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
maxUdc
The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
minUdc
The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
poleLossP
The active power loss at a DC Pole = idleLoss + switchingLoss|Idc| + resitiveLossIdc^2. For lossless operation Pdc=Pac. For rectifier operation with losses Pdc=Pac-lossP. For inverter operation with losses Pdc=Pac+lossP. It is converter’s state variable used in power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_StateVariables-AP-Con-Complex-SHACL_v3-0-0.ttl)
ratedUdc
Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
resistiveLoss
It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
switchingLoss
Switching losses, relative to the base apparent power 'baseS'. Refer to poleLossP. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_Equipment-AP-Con-Complex-SHACL_v3-0-0.ttl)
targetUdc
Target value for DC voltage magnitude. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_SteadyStateHypothesis-AP-Con-Complex-SHACL_v3-0-0.ttl)
uc
Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_StateVariables-AP-Con-Complex-SHACL_v3-0-0.ttl)
udc
Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute shall be a positive value.
- Minimum Value: 0.0
- Source: ENTSOE Application Profiles Library v1.1.0 (61970-301_StateVariables-AP-Con-Complex-SHACL_v3-0-0.ttl)